§ 235-17. Periodic testing.
Latest version.
-
A.Reduced pressure principle backflow devices shall be tested and inspected at least semiannually.B.Periodic testing shall be performed by a certified tester. This testing will be done at the owner's expense.C.Any backflow preventer which fails during a periodic test will be repaired or replaced. When repairs are necessary, upon completion of the repair the device will be retested at the owner's expense to insure correct operation. High-hazard situations will not be allowed to continue unprotected if the backflow preventer fails the test and cannot be repaired immediately. In other situations, a compliance date of not more than 30 days after the test date will be established. The owner is responsible for spare parts, repair tools, or a replacement device. Parallel installation of two devices is an effective means of the owner insuring that uninterrupted water service during testing or repair of devices and is strongly recommended when the owner desires such continuity.D.Backflow prevention devices will be tested more frequently than specified Subsection A above in cases where there is a history of test failures and the Town feels that, due to the degree of hazard involved, additional testing is warranted. Cost of the additional tests will be borne by the owner.